Building Code Amendments
Building Code
Amendments
Building Regulations - Darien Building Code
4-1-1: TITLE, CITATIONS AND SUBSTITUTIONS:
4-1-1-1: TITLE: This Chapter shall be known as the DARIEN
BUILDING CODE.
4-1-1-2: CITATIONS: In citing this Chapter, Section
numbers shall be used except in cases where Codes have been
adopted and incorporated by reference, in which case the
section shall be followed by sections used in such Code
adopted and incorporated by reference.
4-1-1-3: SUBSTITUTIONS: Where Codes have been adopted and
incorporated by reference, the words "City of Darien" shall
be substituted for words referring to the applicable
municipality and where such Codes contain provisions which
are in conflict with specific provisions of this Chapter the
specific provisions of this Chapter shall prevail and shall
rule.
4-1-2: GENERAL PROVISIONS:
4-1-2-1: ESTABLISHMENT OF THE DEPARTMENT OF COMMUNITY
DEVELOPMENT:
(A) There is hereby established a department of the City
known as the Department of Community Development which shall
embrace a Director of Community Development, Senior Planner
and such assistants, clerks and employees as may be
necessary.
(B) All references in the City Code, the Building Code,
the Zoning Ordinance, the Sign Code, the Subdivision
Regulations, the Fire Prevention Code, and in all other
ordinances, resolutions and motions, and rules and
regulations of the City to the "Building Department", the
"Building and Zoning Department", the "Bureau of Fire
Prevention", shall henceforth be construed to refer to and
mean the Department of Community Development.
4-1-2-2: DIRECTOR OF COMMUNITY DEVELOPMENT:
(A) The Director of Community Development shall be
appointed by the Mayor with the advice and consent of the
City Council and subject to removal by the Mayor. The
Director shall be in charge of the Department of Community
Development and shall institute such measures and prescribe
such rules and regulations for the control of subordinate
officers and employees and shall secure the inspection of
buildings while in the process of construction, alteration,
repair or removal, and enforcement of all provisions of the
Building Code.
The Director of Community Development is hereby
authorized to employ, by and with the consent of the City
Administrator, such inspectors or assistants as may be
necessary in the execution of the duties mentioned in the
Building Code or other ordinances as may be from time to
time required.
The Director of Community Development is hereby
authorized to require as a condition to an application and
issuance of a permit that the applicant pay fees in addition
to those otherwise provided herein of review by other than
staff members of plans and specifications.
(B) The duties of the Director of Community Development
shall include, but are not limited to, all of the duties of
the Building Department Supervisor, the Building Official,
the Director of Building and Zoning, the Fire Official, the
Code Official, the Fire Marshall, the Chief of the Bureau of
Fire Prevention, the Zoning Enforcement Officer, the
Building Commissioner, the City Planner, the Building
Inspector, the Building and Zoning Director and the Building
Supervisor as set forth in this City Code, in the Building
Code, in the Zoning Ordinance, in the Sign Code, in the
Subdivision Regulations, in the Fire Prevention Code, and in
all other ordinances, resolutions and motions, and rules and
regulations of the City.
All references in said City Code, the Building Code, the
Zoning Ordinance, the Sign Code, the Subdivision
Regulations, the Fire Prevention Code, and in all other
ordinances, resolutions and motions, and rules and
regulations of the City to the "Building Department
Supervisor", the "Building Official", the "Director of
Building and Zoning", the "Fire Official", the "Code
Official", the "Fire Marshall", the "Chief of the Bureau of
Fire Prevention", the "Zoning Enforcement Officer", the
"Building Commissioner", the "City Planner", the "Building
Inspector", the "Building and Zoning Director" and the
"Building Supervisor" shall henceforth be construed to refer
to and mean the Director of Community Development.
4-1-3: SINGLE-FAMILY DWELLINGS, DUPLEXES AND TW0-FLAT
BUILDING CONSTRUCTION REGULATIONS AND STANDARDS:
4-1-3-1: ADOPTION OF THE 2006 INTERNATIONAL RESIDENTIAL
CODE: There is hereby adopted and incorporated by reference
as a part of this Section, the Code entitled, "2006
International Residential Code", three (3) copies of which
are on file in the office of the City.
4-1-3-2: AMENDMENTS TO CODE: The 2006 International
Residential Code, as adopted in Section 4-1-3-1 of this
Chapter shall be amended as follows:
(A) Section 101.1 - Insert the "City of Darien" for [Name
of Jurisdiction].
(B) Section R-108.2 Revise to read as follows:
See City Code of Darien for appropriate fee schedules.
(C) Section R-113.4 - Revise to read as follows:
Violation penalties: See the City Code of Darien for
penalties for violations of the provisions of this Code.
(D) Section R-1006.1 - Revise to read as follows:
R1006-1 Exterior Air: Factory-built or masonry
fireplaces covered in this chapter shall be equipped with an
exterior air supply to assure proper fuel combustion unless
the room is mechanically ventilated and controlled so that
the indoor pressure is neutral or positive. Ventless or
vent-free fireplaces are prohibited.
(E) Section R-309 - Revise to read as follows:
R-309.9 A ducted cold air return is required in every
sleeping room.
(F) Chapter 26 - Delete. (General Plumbing Requirements)
(G) Chapter 27 - Delete. (Plumbing Fixtures)
(H) Chapter 28 - Delete. (Water Heaters
(I) Chapter 29 - Delete. (Water Supply and Distribution)
(J) Chapter 30 - Delete. (Sanitary Drainage)
(K) Chapter 31 - Delete. (Vents)
(L) Chapter 32 - Delete. (Traps)
(M) Chapter 33 - Delete. (General Requirements)
(N) Chapter 34 - Delete. (Electrical Definitions)
(O) Chapter 35 - Delete. (Services)
(P) Chapter 36 - Delete. (Branch Circuit and Feeder
Requirements)
(Q) Chapter 37 - Delete. (Wiring Methods)
(R) Chapter 38 - Delete. (Power and Lighting
Distribution)
(S) Chapter 39 - Delete. (Devices and Luminaries)
(U) Chapter 40 - Delete. (Appliance Installation)
(V) Chapter 41 - Delete. (Swimming Pools)
(W) Chapter 42 - Delete. (Class 2 Remote Control
Signaling and Power-Limited Circuits)
(X) 2006 International Residential Code electrical
provisions/national code cross reference (appendix Q) -
Delete.
(Y) Agricultural exception: Accessory buildings on
existing, legal nonconforming agricultural properties that
are utilized as stables and livestock shelters, where no
vehicle storage will take place will be allowed in
accordance with the following requirements:
1. Required concrete floor slabs may be omitted in those
specific areas of livestock buildings or structures used by
the livestock upon approval of the Director of Community
Development.
2. Other than in subsection (Y)1 of this Section, floors
shall be concrete, asphalt or wood installed to prevent the
seepage of hazardous, toxic or combustible liquids into the
ground.
3. All accessory buildings shall be securely anchored to
the ground.
4. Preengineered accessory building kits shall be
installed in accordance with manufacturer's specifications
and plans.
4-1-3-3: APPLICATION TO BUILDINGS AND STRUCTURES: The
rules and regulations adopted in Section 4-1-3-1 of this
Chapter shall apply to the following buildings and
structures:
(A) Single-family detached residences.
(B) Duplex houses (2 units side by side) and two-family
apartments or flats.
(C) Detached accessory structures.
4-1-4: REGULATIONS AND STANDARDS FOR CONSTRUCTION OF ALL
OTHER BUILDINGS, INCLUDING RESIDENTIAL (OTHER THAN ONE- AND
TWO-FAMILY), ASSEMBLY, COMMERCIAL, OFFICE, STORAGE,
EDUCATIONAL, INDUSTRIAL AND INSTITUTIONAL:
4-1-4-1: ADOPTION OF THE 2006 INTERNATIONAL BUILDING
CODE: There is hereby adopted and incorporated by reference
as part of this Section, the Code entitled the "2006
International Building Code", three (3) copies of which are
on file in the office of the City.
4-1-4-2: AMENDMENTS TO CODE: The 2006 International
Building Code, as adopted in Section 4-1-4-1 of this Chapter
shall be amended as follows:
(A) Section 101.1 - Insert the "City of Darien" for [Name
of Jurisdiction].
(B) Section 108.2 Revise to read as follows:
See City Code of Darien for appropriate fee schedules.
(C) Section 113.4 Revise to read as follows:
Violation penalties: See City Code of Darien for
penalties for violations of the provisions of this Code.
(D) Section 114.3 Revise to read as follows:
A fine of not less than $100.00 or more than $1,000.00
for each day the above violation shall be imposed.
(E) Section 903.2.1.1 Revise to read as follows:
An automatic fire suppression system shall be provided in
use Group A-1 occupancies when a structures gross square
footage is 2,500 square feet or more.
(F) Section 903.2.1.2 Revise to read as follows:
An automatic fire suppression system shall be provided in
all use Group A-2 occupancies.
(G) Section 903.2.1.3 Revise to read as follows:
An automatic fire suppression system shall be provided in
all use Group A-3 occupancies when a structures gross
square footage is 2,500 square feet or more.
(H) Section 903.2.1.4 Revise to read as follows:
An automatic fire suppression system shall be provided in
all use Group A-4 occupancies when a structures gross
square footage is 2,500 square feet or more.
(I) Section 903.2.5 Revise to read as follows:
An automatic fire suppression system shall be provided in
all use Group I occupancies.
Exception:
1. Where use Group I-2 child care facilities are located
in R-3 and R-4 occupancies in compliance with the Illinois
Department of Child and Family Services.
(J) Section 903.2 Revise to read as follows:
An automatic fire suppression system shall be provided in
all use Group B, E, F, M and S occupancies when a
structures gross square footage is 2,500 square feet or
more.
4-1-4-3: APPLICATION TO BUILDINGS AND STRUCTURES: The
Building Code adopted in Section 4-1-4-1 of this Chapter
shall apply to all buildings and structures other than one-
and two-family residences and other buildings normally
accessory to them.
4-1-5: REGULATIONS AND STANDARDS GOVERNING THE
CONSTRUCTION AND USE OF MECHANICAL EQUIPMENT:
4-1-5-1: ADOPTION OF THE INTERNATIONAL MECHANICAL CODE:
There is hereby adopted and incorporated by reference as
part of this Section, the Code entitled "2006 International
Mechanical Code", three (3) copies of which are on file in
the office of the City.
4-1-5-2: AMENDMENTS TO CODE: The 2006 International
Mechanical Code as adopted in Section 4-1-5-1 of this
Chapter shall be amended as follows:
(A) Insert "The City of Darien" wherever the code refers
to jurisdiction.
(B) Wherever fee schedules, dollar amounts, offenses, or
time limits are referred to in this code, the code of the
City of Darien shall apply.
(C) Section 927 Revise to read as follows:
Ventless and vent free fireplaces are prohibited.
4-1-6: STANDARDS AND SPECIFICATIONS, RULES AND
REGULATIONS OF THE NATIONAL ELECTRICAL CODE:
4-1-6-1: ADOPTION OF THE NATIONAL FIRE PROTECTION
ASSOCIATION NATIONAL ELECTRICAL CODE, 2005 EDITION: The
standards and specifications, rules and regulations of the
National Fire Protection Association National Electrical
Code, 2005 Edition, as published by the national fire
protection association except as amended herein, are hereby
adopted as the standards and specifications, rules and
regulations for installation, alteration, repair and use of
electrical equipment, subject however, to the additional
standards and specifications, rules and regulations as
hereinafter set forth, and except where they are in conflict
with the other provisions of this Code and said Code is
hereby incorporated herein by reference.
4-1-6-2: AMENDMENTS TO CODE: The National Fire Protection
Association National Electrical Code, as adopted in Section
4-1-6-1 of this Chapter shall be amended to read as follows:
(A) Article 394- Concealed Knob End Tube - Delete.
(B) Article 334 - Nonmetallic-Sheathed Cable - Delete.
(C) Article 330 - Metal Clad Cable; Shielded Nonmetallic
Sheathed Cable; 338 Service Entrance Cable. The provisions
of these articles may be permitted only upon written
authorization of the Building Official after sufficient
justification as to the special circumstances making
necessary such permission.
(D) Article 352 - Rigid Nonmetallic Conduit. The
provisions of this Article may be permitted only upon the
written authorization of the Building Official after
sufficient justification as to the special circumstances
making necessary such permission.
4-1-7: PLUMBING INSTALLATION, ALTERATION AND USE
REGULATIONS AND STANDARDS:
4-1-7-1: ADOPTION OF THE PLUMBING CODE OF THE STATE OF
ILLINOIS: There is hereby adopted and incorporated by
reference as part of this section, the code entitled
"Illinois State Plumbing Code 2004 Edition", three (3)
copies of which are on file in the office of the City.
4-1-7-2: ADDITIONS TO CODE: Additions to the Illinois
State Plumbing Code, as adopted in Section 4-1-7-1 of this
Chapter, are as follows:
(A) The installation of water conserving plumbing
fixtures in all new construction and in all repair and/or
replacement of fixtures shall be required according to the
following table:
| Fixtures |
Maximum Flow * |
| Water closets, tank top |
2.5 gals per flush |
| Water closets,
flushometer type |
3.0 gals per flush |
| Urinals, tank type |
3.0 gals per flush |
| Urinals, flushometer
type |
3.0 gals per flush |
| Shower heads |
3.0 GPM |
| Lavatory, sink faucets |
3.0 GPM |
| *Note: Flow based on 40
to 50 psi pressure. |
|
(B) Closed water systems shall be required on all water
using air conditioning systems in new construction or
remodeling.
(C) Metering or self-closing faucets shall be required on
all lavatories for public use in new construction or
remodeling.
(D) Water recycling systems shall be required on all new
construction or remodeled car wash equipment installations.
4-1-7-3: AMENDMENTS TO CODE: The Illinois State Plumbing
Code, as adopted in Section 4-1-7-1 of this Chapter shall be
amended as follows:
(A) Table A - Items 3) and 4) add footnote 3 for Type M
copper. Type M copper is not permitted for water
distribution systems.
(B) All drain lines must be permitted smaller than four
inch (4") diameter material.
4-1-8: FIRE PREVENTION AND CONTROL REGULATIONS AND
STANDARDS:
4-1-8-1: ADOPTION OF THE BASIC/NATIONAL FIRE PREVENTION
CODE OF THE BUILDING OFFICIALS AND CODE ADMINISTRATORS
INTERNATIONAL, INC.: There is hereby adopted and
incorporated by reference as part of this Section, the Code
entitled"2006 International Fire Code", printed in pamphlet
form by the Building Officials and Code Administrators
International, Inc., including no errata sheets inserted,
three (3) copies of which are on file with the City.
4-1-8-2: AMENDMENTS TO CODE: The 2006 International Fire
Code, as adopted in Section 4-1-8-1 of this Chapter shall be
amended as follows:
(A) Section F-101.1 Insert "City of Darien" for [Name
of Jurisdiction].
(B) Section 108 Revise Board of Appeals to read:
Whenever the Chief of the Bureau of Fire Prevention shall
disapprove an application, or refuse to grant a permit, or
when it is claimed that the provisions of this article have
been misconstrued or wrongly interpreted, the applicant or
person affected may appeal from the decision of the Director
of Building and Zoning to the Planning and Zoning Commission
of the City of Darien. Appeals made pursuant to this section
shall be in accordance with the procedures set forth in the
City's Zoning Ordinance.
(C) Section 503.1 Revise to read:
Fire apparatus access roads shall be provided so that:
1. Public or private access is provided to each building
so that the first responding fire district pumper unit will
be able to be so located that all points of the interior of
the building may be reached by one hundred fifty (150) feet
of initial attack hose.
a. Where the size of the building does not allow this
regulation to be met, an interior standpipe system equipped
with fire department hose connections approved by the Fire
Official may be allowed as an exception. The standpipe
system shall be connected to a public water system.
2. Public or private access for motor fire apparatus
shall be provided around the building so that there may be
proper operation of ladders and mechanically elevated
mechanisms.
3. Access routes shall be so arranged that fire
department apparatus may respond from all points of the
building to adjacent fire hydrants along routes not to
exceed two hundred fifty (250) feet from the most remote
point of the building to the closest fire hydrant.
4. Fire lanes on private property shall be approved by
the Fire Official, and parking of motor vehicles otherwise
obstructing such fire lanes or access routes shall be
prohibited at all times. Permanent all-weather signs
identifying fire lanes and access ways shall be posted.
5. In commercial developments public or private fire
department access roads and ways shall be all weather,
properly maintained and accessible at all times. A minimum
of eight (8) inches of granular stone surfaced by at least
two (2) inches of bituminous asphalt material. Fire lanes in
residential developments shall be reviewed by the Fire
Official for adequacy.
6. Access roads or fire lanes shall be not less than
fifteen (15) feet from the building and further if the
height of the building requires a greater setback to ladder
the buildings.
7. Access routes shall be continuous around the building.
a. This requirement may be modified by the Fire Official
where adequate building access openings, a complete fire
suppression system and high rise provisions are provided.
(D) Add Section 316 Revise to read:
Section 316.0 Fire Department Rapid Entry System.
Section 316.1 General. The Fire Official shall require
all new and existing construction that is required to be
equipped with an approved fire alarm system that consists of
smoke and/or heat detection and all buildings required to be
equipped with a complete sprinkler system to have an
approved key box system except of 1 and 2-family dwellings
thirty (30) days after approval of ordinance.
Section 316.2 Purpose. The purpose of the rapid
entrance key system is to allow the fire department to gain
immediate access to a building in emergency situations
without forcible entry.
Section 316.3 Location. The approved key box shall not
be located more than 5 feet from the adjacent grade, and
shall be approved by the Code Official.
Section 316.4 Contents. The approved key box shall
contain key, keycards, etc. needed to gain necessary access
as required by the Code Official.
Section 316.5 Alarms. At the request of the owner or
lessee, the Fire Code Official shall permit him to install a
key box tamper switch connected to the building's alarm
system. If the owner or lessee chooses to connect the key
box to an alarm, then they shall comply with the following
requirements:
1. If the building is protected by a burglar alarm
system, the key box shall be connected to that system.
2. If the building is not protected by a burglar alarm
system, the key box may be connected to the fire alarm
providing the connection is on the trouble side signaling an
alarm. Connection to the fire alarm requires the key box to
be zoned separately from any fire detection and noted on the
fire alarm annunciator panel as KEY BOX.
(E) Add Section 317 to read:
Section 317.0 Miscellaneous Provisions.
Section 317.1 Hazardous Areas - Room used for storage,
boiler or furnace rooms, fuel storage, janitors' closets,
and maintenance shops shall be separated from other building
areas by assemblies having a fire resistance rating of not
less than one hour with appropriate protection of openings
into the rooms.
Section 317.2 Fire Evacuation Procedure Notice. Owners,
managers, and agents of multiple dwelling units with three
(3) or more units, motels, hotels and places of assembly,
served by a common entrance, shall post and maintain in a
conspicuous location within each dwelling unit and in access
routes, a written notice which explains what procedures to
use in the event of a fire. The notice shall contain a
diagram of all fire exits.
(F) Add Section 318 Packing Materials. Materials used
for protective packing shall be kept in approved
noncombustible containers.
Section 318.1 Removal of Packing and Waste Materials.
No persons shall store in any building excess amounts of
combustible empty packing cases, wooden or plastic pallets,
barrels, boxes, rubber tires, shavings, excelsior, rubbish,
paper bags, litter, hay, straw and similar combustibles.
Aisle ways and storage of the abovementioned combustibles
necessary for the performance of business shall be kept in
an orderly and neat manner. Combustible materials shall be
removed daily or more often as is necessary to suitable
vaults, bins, dumpsters, compactors or separate buildings.
Such practices shall be as approved by the Fire Official.
(G) Section 505.1 Address Numbers. In the third line
from the bottom, delete "or alphabet".
(H) Section 806.1.1 Restricted Occupancies. Revise to
read as follows:
Natural cut trees shall only be permitted in the dwelling
units of Group R-2 and R-3 occupancies.
(I) Section 807.4.3.1 Storage in Corridors and Lobbies.
Delete exceptions 1 and 2.
(J) Section 807.4.4.1 Storage in Corridors and Lobbies.
Delete exceptions 1 and 2.
(K) Add Sections 901.7.1 and 901.7.2 to read:
Section 901.7.1 Systems Out of Service. Automatic fire
suppression systems shall not be out of service for more
than eight (8) hours for additions, alterations, maintenance
or repairs without the approval of the Fire Official or the
designated representative.
Section 901.7.2 Control Valve Operator/Fire Watch. When
any fire suppression system must be taken out of service,
for any length of time, a responsible person shall be
stationed at the control valve(s) to immediately activate
the system in case of fire.
(L) Section 905 Standpipe Systems. Add the following:
Class I standpipe systems shall be installed in all
buildings where any portion of the buildings interior area
is more than two hundred (200) feet of travel from the
nearest point of fire district vehicle access.
(M) Add Section 905.12 to read:
Section 905.12 Standpipe Flow Switch. All standpipe
systems shall have flow switches interconnected to the
building fire alarm system.
(N) Section 906.1 Where Required. Add the following:
7. Within five (5) feet of all exit doors in all but
Group R-3 occupancies, and within seventy-five (75) feet of
travel distance. If there are practical difficulties in
locating the fire extinguisher within five (5) feet of an
exit door, then the fire extinguisher shall be located as
directed by the Code Official.
(O) Revise Section 907 to read:
Section 907 Fire Alarm and Automatic Detection
Required.
Section 907.1 All Other Use Groups Except R-3. In all
buildings with floor areas greater than two thousand (2,000)
square feet, automatic and manual fire alarm systems shall
be required and approved by the Code Official for the
particular application and shall only be used for detection
and signaling in the event of fire. Detection devices shall
be compatible with the hazards and purpose for alarm.
Each building which is required to be built pursuant to
the2006 International Building Code as adopted by the City
of Darien, shall be equipped with a wireless radio
connection, approved by the Code Official, between its
automatic fire detection equipment and such appropriate
dispatch station as utilized by the Fire Protection District
or Department which services the structure.
Assembly. Both new and existing educational and
institutional use groups shall be equipped with an approved
fire alarm system. This shall include assembly and
educational uses with 20 or more occupants.
Section 907.2 Alarm systems in Use Group R-1, R-2 and
R-3 (except for detached single-family dwelling structures)
shall comply with the following: Approved automatic fire
protection shall be provided to protect new and existing
multi-family buildings, which include apartments of three
(3) or more units, townhouses and similar uses.
1. Approved automatic smoke detection devices wired to an
activated living unit electrical circuit shall be provided
in the vicinity of all bedrooms and elsewhere, based on room
arrangements, in each living unit.
(a) The wiring shall allow for easy removal and
replacement of the device.
(b) Each detector shall include an audible alerting
device.
i. Approved fixed temperature devices shall be provided
in each living unit near the kitchen and living room areas,
with not less than one installed on each floor level. These
shall be part of the fire alarm system.
ii. Generally unattended areas such as storage rooms,
garages, combustible unattended areas, elevator shafts,
furnace rooms, basements, attic spaces, crawl spaces and
similar areas shall be protected by approved heat detection
devices.
iii. Approved smoke detection devices shall be provided
in all public or common egress routes, including corridors,
stairways, exit hallways, etc.
iv. All devices, except living unit smoke detectors (from
(a) above), shall be interconnected to an approved control
panel with an audible alerting system servicing all floors
of the building.
v. A zone indicator panel shall be provided in any
building having multiple living units, with each zone
serving more than one floor.
2. Assembly. Both new and educational and institutional
use groups shall be equipped with an approved fire alarm
system.
Section 907.3 Design. The system shall be designed and
installed in accordance with the National Fire Protection
Association No. 72, Installation, Maintenance and Use of
Protective Signaling Systems, 2007 Edition, with automatic
detectors designed and installed in accordance with the
National Fire Protection Association.
Section 907.4 Power Supplies. A primary power supply
source for the operation of the system under normal
conditions shall be provided. A secondary power supply for
operation of the system shall be by an U.L. approved energy
device or minimum 60-hour storage battery or engine driven
generator.
Section 907.5 No alarm shall be out of service for more
than 24 consecutive hours.
Section 907.6 Automatic Sprinklers. Where automatic
sprinklers provide protection to an area, approved flow and
tamper switches interconnected to the fire alarm system
shall be provided.
Section 907.7 Zones. Each floor and each area over
15,000 square feet in area shall be separately zoned. Each
type of system (sprinkler, halon, alarm, etc.) shall be
separately zoned.
Section 907.8 Each sprinkler system need only be zoned
per floor for a flow alarm.
Section 907.9 The fire protection district shall have
access at any time of the day or night to the fire alarm
control panel without entering an individual living
(dwelling) unit. The fire alarm panel must be installed in
an approved climate controlled, weather protected closet
with 24-hour access from the exterior of the building.
(P) Add Section 915 to read:
Section 915 Fire Hydrant Locations.
Section 915.1 Fire Hydrant Locations. Water supplies
shall be delivered under pressure to fire hydrants located
as follows:
1. Fire hydrants shall be located along public streets,
fire lanes, or access routes so that no portion of the
building will be over 250 feet from a public fire hydrant.
Where this is not possible, additional hydrants shall be
located on the premises and be accessible to motorized fire
apparatus.
2. In apartments, townhouses, condominiums, town/row or
cluster housing areas where streets or parking lots dead
end, hydrants shall be placed along the access route at a
location approved by the fire official.
3. At least two (2) fire hydrants shall be located within
300 feet of the building.
4. Hydrants should be so located that:
a. Hydrants will be located approximately ten (10) feet
from all weather roadways. If this cannot be done, the
closest part of the hydrant shall be set back at least two
(2) feet from the curb.
b. Hydrants shall not be located further than 75 feet
from any fire department sprinkler or standpipe connection
as determined by the Code Official.
c. Hydrants shall not be located closer than 25 feet to a
building.
d. Hydrant outlets shall be a minimum of 18 inches but
not more than 36 inches above the finished grade.
e. Access to fire hydrants shall be all-weather roadways
adequate in width, clearance and strength for fire fighting
purposes. Such routes including private roadways, shall be
maintained accessible during all seasons of the year.
5. Fire hydrants used in conjunction with water supplies
shall have two (2 1/2) inch and one (4 1/2) inch outlets
with auxiliary gate valves on the hydrant branch line.
Threads shall be American National Standard. Pumper outlets
shall face roadways.
6. Fire hydrants shall be protected from accidental
damage by approved methods when located in areas subject to
vehicular damage.
(Q) Section 1006.3 Illumination emergency power revise
to read as follows:
Emergency lighting shall be equipped with power supplies
from an independent, approved reliable source (battery or
automatic starting generator). Emergency lighting shall be
provided in all rooms and spaces over 2,000 square feet in
area, or in rooms with an occupancy load of 20 or more. When
required, emergency lighting shall be installed in
stairways, corridors, access routes and other exit
components. Multi-family building - emergency lighting will
be required in all existing and new multi-family buildings
in stairways, corridors, exit access and other exit
components.
(R) Add Section 1004.10 Number and Location of Exits.
All rooms or spaces with accommodations for 20 or more
persons or over 2,000 square feet in area and each floor
shall have 2 separate means of egress.
(S) Add Section 3308.12 to read:
Section 3308.12 Bond and Responsibility. Bond and
responsibility for fireworks Display and Discharge requires
"Public Liability Insurance" in the amounts of not less than
$1,000,000.00 bodily injury and $250,000.00,. The City of
Darien and the local Fire Protection District shall be added
as an "Additional Insured."
(T) Add Section 3406.9 to read:
Section 3406.9 Special Dispensers. Special type
dispensers such as coin, key or card- operated devices, for
self service operation by the general public are prohibited
unless there is an attendant on duty at all times.
(U) Delete Sections 803.4.3.1.1 and 803.4.3.1.2.
(V) Chapter 45, Reference Standards: Revise the NFPA
Standard Reference Numbers as follows:
From 13-02 to 13-07
From 13D-02 to 13D-7
From 13R-02 to 13R-07
4-1-8-3: DEFINITIONS AND ADDITIONAL REGULATIONS OF THE
2006 INTERNATIONAL FIRE CODE:
(A) Definitions:
1. FIRE PREVENTION CODE OR CODE: Wherever the words "Fire
Prevention Code" or "Code" are used in the codes adopted
herein by reference, they shall be to mean the City of
Darien 2006 International Fire Code.
2. MUNICIPALITY: Wherever the word "municipality" is used
in the Codes adopted herein by reference, it shall be held
to mean the City of Darien.
3. CITY: Wherever the word "City" is used in the codes
adopted herein by reference, it shall be held to mean the
City of Darien.
4. CORPORATION COUNSEL: Wherever the term "corporation
counsel" is used in the Codes adopted herein by reference,
it shall be held to mean the legal counsel for the City of
Darien.
5. FIRE OFFICIAL, CODE OFFICIAL, FIRE MARSHALL, AUTHORITY
HAVING JURISDICTION OR CHIEF OF THE BUREAU OF FIRE
PREVENTION: Wherever the term "Fire Official", "Code
Official", "Fire Marshal", "Authority Having Jurisdiction"
or "Chief of the Bureau of Fire Prevention" is used in the
codes adopted herein by reference, it shall be held to mean
the Director of Building and Zoning or his designee.
6. BUREAU OF FIRE PREVENTION: Wherever the term "Bureau
of Fire Prevention" is used in the Codes adopted herein by
reference, it shall be held to mean Department of Community
Development.
(B) Administrative Bodies:
1. The Fire Prevention Code shall be enforced by the
Department of Community Development of the City.
2. The person in general charge of the Department of
Community Development shall be the Director of Community
Development.
3. The Director of the Community Development may detail
additional personnel as inspectors to assist in enforcing
this Chapter.
(C) Application of Provisions: Except as stated elsewhere
in this Chapter, any existing building and/or structure
shall be brought into compliance with all applicable
provisions of the Fire Prevention Code in the following
situations:
1. If the structure or building is increased in floor
area or in height, the entire structure or building shall be
made to conform with the requirements of this Chapter.
2. If any portion is changed in occupancy, that portion
separated by approved fire- rated construction shall be made
to conform with the requirements of this Chapter.
3. If any portion is altered or remodeled costing in
excess of fifty percent (50%) of the fair market value of
the building or structure, such building or structure shall
be made to conform to the requirements of this Chapter.
4. If a building or structure is damaged by fire or other
cause to the extent in excess of fifty percent (50%) of the
fair market value before the damage was insured, the entire
structure or building (exclusive of foundation) shall meet
the requirements of this Chapter.
(D) Permits And Approvals:
1. Special Permits: Where special permits are required,
application shall be made to the Director of the Department
of Community Development. The Director shall determine
criteria, limitations and duration of permits until the
appropriate requirements are met.
(E) Explosives And Blasting Agents:
1. The storage, handling and use of explosives and
blasting agents is prohibited within the City.
(a) Exception: By special permit from the Director of the
Department of Community Development.
(F) Flammable Liquids; Liquefied Petroleum Gases:
1. The storage of flammable liquids in outside
aboveground tanks is prohibited.
(a) Exception: By special permit from the Director of the
Department of Community Development.
2. The bulk storage of liquefied petroleum gases in
excess of one thousand (1,000) gallons water capacity is
prohibited.
(a) Exception: By special permit from the Director of the
Department of Community Development.
(G) Manufacturing And Storage Of Fireworks Prohibited:
The manufacture and storage of fireworks is prohibited
within the corporate limits of the City, except by special
permit issued by the Code Official.
(H) Motor Vehicle Routes For Vehicles Transporting
Hazardous Chemicals Or Other Dangerous Articles, Including
Liquefied Petroleum Gases And Combustible And Flammable
Liquids: The routes referred to in section 20.14 of the Fire
Prevention Code for vehicles transporting hazardous
chemicals and other dangerous articles are hereby
established as routes approved by State, County or Federal
governments.
No tank vehicles shall be parked for over one hour or
left unattended at any time.
(I) Emergency Conditions: When in the opinion of the
Director of the Department of Community Development or his
designee there is actual and immediate danger because of
hazardous conditions which endanger life or may cause
effects upon adjoining properties, the Bureau may order the
building to be immediately vacated and cause immediate
remedial action if necessary. The cost of such remedial
action shall be borne by the owner of the premises.
(J) Modifications: The Director of the Department of
Community Development and the City Administrator shall have
power to modify any of the provisions of the Fire Prevention
Code upon application in writing by the owner or lessee, or
his duly authorized agent, when there are practical
difficulties in the way of carrying out the strict letter of
the Code; provided that the spirit of the Code shall be
observed, public safety and substantial justice done. The
particulars of such modification, when granted or allowed,
and the decision of the Fire Marshall shall be entered upon
the records of the Department and a signed copy shall be
furnished the applicant.
(K) New Materials, Processes Or Occupancies Requiring
Permits: Upon a written request to employ new materials,
processes or occupancies which require a permit or otherwise
alter the provisions of the Fire Code, in addition to those
now enumerated in said Code, the Director of Community
Development shall forward said request along with supporting
documentation and other applicable information as determined
by the Director of Community Development and City
Administrator to the building plan review and building
inspection consultants employed by the City, to the local
Fire District and when applicable, to the City Engineer, for
their review and recommendation. Upon receipt of the
recommendations from these sources, the Director of
Community Development and City Administrator shall either
approve or deny said request. In either situation, the
determination made shall be posted in a conspicuous place at
the Darien City Hall, and copies shall be distributed to all
parties.
(L) Penalties: The penalty for violation of this code
shall be in accordance with the City Code penalty Section.
4-1-9: EXISTING STRUCTURES REGULATIONS:
4-1-9-1: ADOPTION OF INTERNATIONAL PROPERTY MAINTENANCE
CODE: There is hereby adopted and incorporated by reference
as part of this Section, the Code entitled "2006 The
International Property Maintenance Code", printed in
pamphlet form by the International Code Council, including
no errata sheets inserted therein as modified in certain
respects as set forth herein, three (3) copies of which are
on file in the office of the City.
4-1-9-2: AMENDMENTS TO CODE: The International Property
Maintenance Code, as adopted in Section 4-1-9-1 of this
Chapter shall be amended as follows:
(A) Section 101.1 Insert "City of Darien for [Name of
Jurisdiction].
(B) Section 106.4 Penalties. Revise to read as follows:
See the City Code of Darien for penalties for violations
of the provisions of this Code.
4-1-10: PERMITS AND FEES:
4-1-10-1: PERMIT REQUIRED; ISSUANCE: A building permit,
as provided for herein, shall first be required before any
construction, alteration, repair or removal within the City
shall be commenced. No work shall be done and no permit as
required by these regulations shall be issued until the fee
prescribed therefore has been paid and all other
requirements for such permit have been met.
4-1-10-2: GENERAL REQUIREMENTS:
(A) Plat Of Survey With Application: A plat of survey
shall be submitted with a building permit application. The
plat of survey shall be prepared by a registered land
surveyor of the state of Illinois and include topographical
data showing existing contours at vertical intervals of not
less than two feet (2'), proposed changes in contours,
proposed foundation and elevations and other land
improvements within the platted property and surrounding
properties. Topographical data shall refer to true USGS
elevation standards.
(B) Spotted Survey Required: Two (2) copies of a spotted
survey will be required within fourteen (14) days after the
foundation is placed on the lot. The spotted survey shall
include the true USGS elevations of the top of foundation
wall and existing grade of curb, sidewalk or existing grade
of street or roadway. It shall also include all building
setbacks from the property boundaries. No construction will
be permitted past the decking over the foundation except for
water, sanitary sewer and related items unless such survey
has been filed and approved by the Department of Community
Development staff.
(C) Final Grading Survey Required: Two (2) copies of a
final grading survey will be required no less than four (4)
days prior to the request for final occupancy. The final
grading survey shall include topographical data showing
final contours at vertical intervals of not less than two
feet (2) based on true USGS elevation standards. A
certificate of occupancy will not be issued until the final
grading survey is approved by the City Engineer.
In any residential zoning district, no permit may be
issued for additional work if there remains uncompleted
other work on the premises for which a building permit has
been issued for more than twelve (12) months.
(D) Duration Of Permits:
1. Duration: The duration of a building permit shall be
one year from the date of issuance.
2. Permit Extensions: Upon approval of the Building
Official, a building permit may be extended for a period not
to exceed six (6) months on payment of fifty percent (50%)
of the original building permit fee.
3. One Permit Limit: No more than one building permit
shall be issued for a property unless construction required
under the first building permit continues at a reasonable
level.
4. Suspension Of Permit: Any building permit issued, but
under which no work has commenced within six (6) months
after issuance of the permit, or if the authorized work is
suspended or abandoned for a period of six (6) months after
the time of commencing, the permit shall expire by its own
terms. The permit must be surrendered to the building
inspector within ten (10) days after its expiration, and
fees paid therefore shall be forfeited to the City. Upon
such surrender, fifty (50) percent of the total permit fee
shall be refunded.
(E) Contractor Registration Requirements:
1. All contractors, except electrical and plumbing
contractors, shall obtain a city contractor's license. This
shall include all subcontractors. The Darien contractor's
license year runs from May 1 to April 30. There is an annual
fee with a one-half (1/2) year fee after November 1.
2. Electrical contractors shall give evidence of good
standing by supplying a copy of the registration with any
other city, county or state jurisdiction in Illinois.
3. Plumbing contractors must be licensed with the state
of Illinois and shall submit a copy of their license.
Plumbing contractors doing sewer work shall be required to
obtain a contractor's license.
4. Roofing contractors must be licensed with the state of
Illinois and shall submit a copy of their license and shall
be required to obtain a contractor's license.
5. All contractors including plumbing, electrical and
roofing contractors, shall submit the following to the City:
(a) A ten thousand dollar ($10,000.00) license bond. The
general contractor may submit a twenty thousand dollar
($20,000.00) license bond in lieu of separate bonds on each
subcontractor.
6. License bond requirement may be waived where the owner
of a single-family house is acting as a general contractor.
(F) Construction Vehicle Driveways: For any construction
which does not include a hard surface for construction
vehicles, a stone driveway must be laid within five (5) days
of the placement of a foundation on a property.
(G) Erosion Control Devices: Erosion control devices such
as silt fencing or hay bales shall be erected around the
perimeter of any property under construction which includes
earthwork.
(H) Sidewalk Construction Required Along Major Arterial
Streets:
1. The City shall not issue any building permits for
construction taking place along "major arterial streets", as
defined hereafter, unless the applicant for the building
permit and the owner of the property shall execute an
acknowledgment that no occupancy permit for the building or
structure will be issued unless sidewalks, constructed in
accordance with the ordinances of the City, are installed
along such major arterial streets prior to the occupancy of
the building or structure. In lieu of the installation of
the sidewalk prior to occupancy, and at the option of the
City, the owner of the property may post a cash deposit with
the City equal to the then current cost of installing the
sidewalk or such other security acceptable to the City. This
cash sum or other security shall be retained by the City
until such time as it is most convenient for the City to
install or to have installed such sidewalk segment either
singly or as part of a larger sidewalk construction program.
If, at the time the sidewalk is eventually installed, the
cost of installing the sidewalk shall exceed the amount of
the cash sum or other security posted, the owner shall be
obligated, upon thirty (30) days' written notice, to
increase the amount of that cash sum or other security in an
amount sufficient to enable the City to install or to have
installed the sidewalk. In the event that the cost of
installing the sidewalk shall be less than the cash sum or
other security deposited with the City, the amount of such
excess will be returned to the owner after the sidewalk is
installed and all costs for the installation of the sidewalk
have been paid.
2. For the purpose of this subsection, "major arterial
streets" within the City shall be defined as follows:
(a) Route 83.
(b) Clarendon Hills Road.
(c) Plainfield Road
(d) Cass Avenue.
(e) 75th Street.
(f) Bailey Road.
(g) North and South Frontage Roads.
(h) Manning Road.
(i) Lemont Road
(j) 83rd Street
3. Any person who violates any provision of this
subsection (H) shall upon conviction thereof be fined not
less than fifty dollars ($50.00) nor more than five hundred
dollars ($500.00). Every day upon which a violation of this
subsection (H) takes place shall be deemed to be a separate
offense.
(I) Permitted Hours Of Construction:
1. No construction for which a building permit is
required under this Chapter shall commence before the hour
of six thirty o'clock (6:30) A.M. or continue after the hour
of ten o'clock (10:00) P.M. on Monday through Friday, or
commence before the hour of seven thirty o'clock (7:30) A.M.
or continue after the hour of ten o'clock (10:00) P.M. on
Saturday or Sunday.
2. Any person who violates any provision of this
subsection (I) shall be fined not less than fifty dollars
($50.00) nor more than five hundred dollars ($500.00) for a
first offense. Any person who violates any provision of this
subsection (I) a second or subsequent time shall be fined
not less than one-hundred dollars ($100.00) nor more than
five hundred dollars ($500.00). In addition, violation of
this provision may be deemed cause for revocation of the
building permit.
4-1-10-3: PERMIT FEES:
(A) Plan Review Fees: Plan review fees are accessed
through outside professional services.
| Single-family residence |
$315.00 |
| Residential additions |
215.00 |
| Detached garage |
115.00 |
| Multi-family residence |
315.00 per dwelling
unit |
| Basement remodeling,
deck, shed, etc. |
115.00 |
| Commercial, office,
industrial |
0.003 x construction
cost as determined by the most current publication
of the Means Cost Estimating Guide |
| Elevators, escalators,
dumb-waiters, platform lifts |
100.00 |
| Parking lots |
100.00 |
| Sign permits |
50.00 |
| Resubmittals |
65.00 for each |
The City reserves the right to employ outside review of
any and all plans submitted and the cost of such review will
be paid by the applicant.
(B) Construction Permit Fees:
1. Computing Fees: For the purposes of computing fees,
all subordinate detached buildings, the use of which is
clearly related to that of the main building located on the
same plot, shall be considered to constitute a part of the
main building when included in the same application for a
building permit or when a permit is obtained for the
detached subordinate building or buildings before occupancy
of the main building.
2. Building Permit: The building permit fee for all new
construction, additions, and alterations shall be based on
the estimated cost of construction including all structural,
electrical, plumbing, mechanical interior finish and site
preparation elements. The following table sets forth said
fees:
|
Construction Cost |
Fee |
| $0.00 - |
$8,000.00 |
$75.00 |
| 8,001 - |
15,000.00 |
150.00 |
| 15,001.00 - |
20,000.00 |
200.00 |
| 20,001.00 - |
25,000.00 |
250.00 |
| 25,001.00 - |
35,000.00 |
500.00 |
| 35,001.00 - |
50,000.00 |
750.00 |
| 50,001.00 - |
75,000.00 |
1,000.00 |
| 75,001.00 - |
100,000.00 |
1,250.00 |
| 100,001.00 - |
150,000.00 |
1,500.00 |
| 150,001.00 - |
200,000.00 |
2,000.00 |
| Over
200,000.00 |
| |
3. Plumbing Permits: A separate plumbing permit shall be
required when plumbing work is not performed in connection
with a required building permit for new construction,
alterations, additions, repairs or accessory uses. The
plumbing permit fee shall be based on the following
schedule:
(a) Residential - $10.00 per fixture
(b) Nonresidential - $20.00 per fixture
4. Electrical Permits: An electrical permit shall be
required when electrical work is not performed in connection
with a required building permit for new construction,
alterations, additions, repairs or accessory uses. The
electrical permit fee shall be based on the following
schedule:
(a) Residential - $ 3.00 per outlet plus 10.00 per
circuit
(b) Nonresidential - $ 3.00 per outlet plus 10.00 per
circuit
5. Elevator Permits:
| Elevator |
$50.00 |
| Escalator |
50.00 |
| Dumbwaiter |
30.00 |
| Movable stage or
orchestra floor |
50.00 |
| Platform lift |
50.00 |
| Hinged platform lift |
50.00 |
All existing elevators shall be inspected annually, at
the cost of the property owner.
6. Permits For Tanks For Flammable Liquids:
(a) Class 1 and 2 (1,000 gallon capacity - $50.00
Each 100 gallons or fraction thereof over 1,000 add
2.00
(b) Class 3 and 4 (550 gallons or less) - $40.00
Each additional 1,000 gallons or
fraction thereof over 550 - add 2.0
7. Other Permits Which May Require Plan Review Fee:
| Fire protection
systems, including but not limited to range hoods,
sprinklers, alarms |
$50.00 |
| Heating system/furnace |
50.00 |
| Residential air
conditioner |
50.00 |
| Commercial conditioner |
150.00 |
| Building demolition |
|
| 500 square feet or less |
50.00 |
| Over 500 square feet |
100.00 |
| Tank removal |
100.00 |
| Swimming pool |
|
| Aboveground |
50.00 |
| Inground |
100.00 |
| Fence |
25.00 |
| Deck |
50.00 |
| Satellite dish |
50.00 |
| Detached garage - (up
to 800 square feet) |
100.00 |
| Shed - (100 to 800
square feet) |
50.00 |
| Steam boiler |
75.00 |
| Incinerator (state
approved) |
|
| 5 square feet or less |
50.00 |
| Each additional 5
square feet |
5.00 |
| Driveways/parking lots |
|
| Residential |
25.00 |
| Nonresidential |
50.00 |
| Other permits |
50.00 |
8. Sign Permits: The erection, construction or alteration
of any sign, or its advertising structure, marquee, canopy
or awning, requires a sign permit based on the following
schedule:
| Nonilluminated signs
(unless temporary) plus $1.00 per square foot of
gross surface area of each face thereof |
$100.00 |
| Temporary signs |
35.00 |
| Marquees, canopies and
awnings plus $0.20 per square foot of gross surface
area |
20.00 |
| Illuminated signs plus
$2.00 per square foot of gross surface area of each
face thereof |
200.00 |
| Reface of existing sign |
100.00 |
| Permanent residential
development sign as described in subsection
4-3-10(A)3 of this Title |
no charge |
9. Other Fees:
| Reinspection |
|
| First occurrence |
$80.00 |
| Second occurrence |
100.00 |
| Work started without
permit |
2 x standard fee |
| Final occupancy |
50.00 |
| Violation of Building
Code |
|
| First offense |
100.00 |
| Subsequent offense |
200.00 |
| Elevator inspection |
50.00 |
(C) Independent Inspectors: The city may, from time to
time, hire an independent inspector to make inspections
which cannot be performed by the staff building inspectors.
The cost of said inspections shall be paid by the builder.
(D) Reinspections: Whenever a reinspection is required,
due to inaccurate information or construction, an additional
fee of eighty dollars ($80.00) shall be charged for the
first reinspection. A one hundred dollar ($100.00) fee shall
be charged for each additional reinspection after the first
reinspection. This fee shall be payable prior to the
reinspection being performed.
(E) Failure To Receive Required Inspection: If a builder
fails to receive a required inspection and continues to
work, there shall be a one hundred dollar ($100.00) fee. A
building inspector may require removal of any unauthorized
work in order to adequately make a required inspection.
(F) Work Started Without A Permit: Whenever work for
which a permit is required is commenced without a permit,
the applicant shall pay the following additional fees:
Fifty dollars ($50.00) for the first three thousand
dollars ($3,000.00) of construction cost, and twenty dollars
($20.00) per one thousand dollars ($1,000.00) of additional
cost of construction in order to reimburse the city for
clerical, inspection and other administrative expenses.
(G) Permit Pickup: Building permits must be picked up
within sixty (60) days of approval. If a permit is not
picked up within sixty (60) days, it will become null and
void and the applicant will be charged the applicable plan
review fee.
(H) Temporary Certificate Of Occupancy (Valid For A
Period Not To Exceed 120 Days):
| Residential |
$100.00 + cash bond for
cost of outstanding work |
| Commercial |
$150.00 + cash bond for
cost of outstanding work |
In addition, the seller/owner of any property for which a
temporary certificate of occupancy is sought shall post the
following sums to ensure the completion of incomplete items
as follows:
| Site grading |
5,000.00 |
| Sidewalk |
15.00 per square foot |
| Concrete driveway
approach/private driveway |
15.00 per square foot |
| Asphalt driveway
approach/private driveway |
10.00 per square foot |
| Private landscaping |
4,000.00 |
| Public landscaping,
infrastructure, storm sewer, storm sewer structure
and water valves. |
3,000.00 |
Such sums shall be released upon the issuance of a final
certificate of occupancy. In the event all or a portion of
said work is not completed by the expiration of the
prescribed period of not to exceed one hundred twenty (120)
days, the City may, in its discretion, release such funds to
the property owner or cause uncompleted work to be
completed.
(I) Final Certificate Of Occupancy: $50.00
4-1-10-4: DUPAGE COUNTY FAIR SHARE TRANSPORTATION IMPACT
FEE: In addition to any other requirements of this code, no
building permit or occupancy permit shall issue for
improvements subject to the requirements of the DuPage
County fair share transportation impact fee ordinance,
county ordinance OTD-021-89, as said ordinance may be
amended from time to time, until the applicant for such
permit furnishes the City with a copy of a receipt of
payment of DuPage County's impact fee.
|